Watlow Series 988LF Instrukcja Użytkownika Strona 44

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 64
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 43
6.4 WATLOW Series 988LF Users Manual Factory Menus, Chapter 6
Test Outputs
This prompt tests each output. To run the test, scroll through the
Diagnostics Menu until [tout] is shown in the lower display. Use the Up-
arrow key > or Down-arrow key < to select an output [out1] or
[out2]. The LED for that output should light after a second or two indicat-
ing that the output has been successfully energized. Do not press the
mode key µ to activate the test; it starts automatically when anything
other than [`OFF] is selected.
If any of the LEDs fail to light contact the factory.
[tout] This prompt always appears.
Default
[`OFF] [out1] [out2]
[tout] [tout] [tout]
Open Loop
Checks the control loop, consisting of the controller output, power
control, heater and sensor. With open loop enabled, the controller moni-
tors the output power level and checks for a change in the process input
value. If the output power is at maximum for a period of time equal to the
reset time and the process input has not changed by at least ±5°F, the
controller will switch to manual mode at 0% output power and [OPLP] will
be displayed in the lower display.
To clear this error, enter the Setup Menu and press the display key . To
get back into auto mode, press the Auto/Man key å.
[OPLP] This prompt always appears.
Default
[`OFF] [``On]
[OPLP] [OPLP]
[tout]
[OPLP]
Factory-Diagnostics
Przeglądanie stron 43
1 2 ... 39 40 41 42 43 44 45 46 47 48 49 ... 63 64

Komentarze do niniejszej Instrukcji

Brak uwag