92 8LS Users Guide
Appendix A: Ramp Soak
Copying the Setup from Another Profile
Use this menu to setup similar profiles quickly, by copying a profile to
another one.
Selectable Values:
A to H.
Editing the Tolerance Alarm Time
Use this menu to set a tolerance time that applies to the entire profile.
When the segment goes out of tolerance,
The segment goes into tolerance hold.
The segment timer holds.
The loops single loop display shows TOHO (Tolerance Hold).
When the segment has been out of tolerance for more than the tolerance
alarm time,
The controller goes into tolerance alarm.
The tolerance timer resets.
You must acknowledge the tolerance alarm by pressing the ALARM
ACK key before you can do any other editing.
Selectable Values:
0:00 to 99:59 (minutes or hours, depending on the
time base setting).
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
R/S PRO
COPY? H
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
A OUTTOL
T? 1:00