56 8LS Users Guide
Setup
Linear Scaling Menus
NOTE
The next four menus appear only for Linear or
Pulse loops.
For all inputs automatic scaling is provided. To set the scaling enter a
high process variable in engineering units and a corresponding high
reading. Then enter a low process variable in engineering units and a
corresponding reading. Using points as near as possible to zero and full
scale is best. After these entries the process variable, the setpoint and
alarms will all be in engineering units.
High PV Display
Selectable range:
0-9999.
High RDG Display
Selectable range:
0-9999.
The high input reading is referenced to 60mV and is calculated using
this equation:
Low PV Display
Selectable range:
0-9999.
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
1 HI PV
? 1000
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
1 HI RDG
? 1000
HIGH RDG = (1000)
(Sensor output @ High PV)
60 mV
*