
Chapter 12: Function Blocks LogicPro User’s Guide
190 Watlow Anafaze Doc.# 28002-00 Rev 3.00
The module address is determined by the rotary switch setting on the
face of the module with the exception of the processor module which
has address zero.
The module I/O number is generally the number on the terminal to
which the I/O device is attached, but see the PPC-2000 User’s Guide
to be certain.
The I/O type in the address is a digit that indicates the type of I/O
addressed. Used when addressing I/O in modules that handle more
than one type. Table 12.7 lists the options for the I/O Type digit in
the three-place address.
Table 12.7 I/O Type Digit in IO Physical
Address
Parameter Specific Drivers
The parameter specific IO Drivers (Setpoint, Soft_Input,
Soft_Bool, and Soft_Int) are used to read or set values for
specific parameters. The specific parameter value is addressed
with its database offset.
The database offset is the location of a particular value
relative to the first value of that parameter. For example, to
access channel 17’s setpoint with the Setpoint IO Driver, the
IO Physical address will consist of the database offset, 17.
Table 12.8 lists the parameter specific drivers and the
corresponding database offset ranges.
Table 12.8 Addresses Used with Parameter
Specific IO Drives
Database Driver
The Database IO Driver is used to examine or set values for
any closed-loop control parameter such as Control Mode that
is not supported by one of the other drivers. The Database
driver allows access to all controller parameters. Other drivers
are provided for faster access to specific parameters. Of
course, controller parameters that are read-only cannot be
adjusted. The specific parameter value is addressed with the
Y I/O Type
0 Digital I/O State
1 Count Value
2 Frequency Value
3 Analog Output Value
IO Driver Database Offset
Setpoint Channel Number (1-48)
Soft_Input Soft Input Number (1-50)
Soft_Bool Soft Bool Number (1-1000)
Soft_Int Soft Int Number (1-100)
Komentarze do niniejszej Instrukcji