Parameters
=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.15
ON
PID Group continued
about PID control.
• Read/write
• Modbus: 502
Range
0.00 to 99.99 minutes per repeat
Default
0.00
Active
if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to US
Affected by
Changing Units Type (System Group) will convert Integral to
Reset.
Derivative
• Set the derivative time for PID control. See Chapter 4 for
information about PID control.
• Read/write
• Modbus: 503
Range
0.00 to 9.99 minutes
Default
0.00
Active
if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to SI
Rate
• Set the rate time for PID control. See Chapter 4 for information
about PID control.
• Read/write
• Modbus: 504
Range
0.00 to 9.99 minutes
Default
0.00
Active
if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to US