Watlow MICRODIN Instrukcja Użytkownika Strona 71

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 106
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 70
Parameters
=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.23
ON
Input Error (see also Input Group)
• Monitor the input error status.
• Read only
• Modbus: 101
Range
0: no error
1: analog-to-digital signal under range
2: sensor under range
3: sensor over range
4: analog-to-digital over signal range
Default
none
Active
always
System Error
• Read the system error status.
• Read only
• Modbus: 209
Range
0: no error
4: RAM error
5: non-volatile checksum error
6: PROM error
7: hardware failure
11: software version change
12: calibration checksum error
13: analog-to-digital failure
14: non-volatile hardware failure
15: new unit
Default
none
Active
always
Error Group – Use
Clear Error
• Try to clear a latched input error.
• Read/write
• Modbus: 311
Range
0: no action
1: try to clear latched input error
Default
0 (always reverts after a write)
Active
always
Error Group continued
Przeglądanie stron 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 105 106

Komentarze do niniejszej Instrukcji

Brak uwag