Watlow Series 945 High/Low Limit Control Instrukcja Użytkownika Strona 13

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 20
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 12
13
WATLOW Series 945 High/Low Limit User's Manual
Operation Parameters Value Range Factory Default
Target Set Point See explanation above.
ALO- Deviation dE -999° to 0° -999
Process Pr rL to AHI rL
AHI- Deviation dE 0° to 999° 999°
Process Pr ALO to rH rH
OFF ± 180°F / ± 100°C0
Figure 15 -
The Operation Menu.
NOTE:
The Upper display
will always return to
the process value
after 1 minute
without key strokes.
ALO
AHI
OFF
Table 3 -
Operation Menu
Prompts and
Descriptions.
Operation Menu
Use this page as a master copy for your Series 945 Operation Parameters.
Do not enter any values here; make photocopies instead.
Target Set Point or Blank: Displays the target set point while using deviation
alarm only. Display remains blank while in the process alarm mode.
Alarm Low: This parameter represents the low process alarm or low deviation
alarm for the mechanical relay alarms.
Range: 0 to -999°F/0 to -999°C/0 to -999 Units Default: -999°F
If AtyP = Pr: Range: rL to AHI Default: rL
Alarm High: This parameter represents the high process alarm or high
deviation alarm for the mechanical relay alarms.
Range: 0 to 999°F/0 to 999°C/0 to 999 Units Default: 999°F
If AtyP = Pr: Range: ALO to rH Default: rH
Calibration Offset: Adds or subtracts degrees from the input signal.
Range: ± 180°F / ± 100°C Default: 0
Operation Parameters
M
ACt
ALO
AHI
CAL
( )
( )
( )
Represents target set point
for deviation alarms, or
remains blank
Mode Key
Operation
OFF
Przeglądanie stron 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 19 20

Komentarze do niniejszej Instrukcji

Brak uwag