Watlow Series SD 40 Chapter 7 Operations for TRU-TUNE+™
7
These parameters can be selected to appear in the Operations Page. Select the parameters you want to appear in
the Operations Page in the Programming Page. Press the Advance Key to enter the Operations Page and to step
through the parameters. For profiling controllers, set [Prog] to [``no] to access the Operations Page. Press the
Infinity Key ˆ to return to the Home Page at any time.
Note: This chapter only applies to the TRU-TUNE+™ version of the Series SD (SD_E - _ _ _ _ - _ _ _ _).
Chapter 7:
Operations Parameters Table
for TRU-TUNE+™
Display Parameter name
Description
Settings Range Default Modbus*
(less 40,001 offset)
Read/Write
Appears if"
[Po;ht]
[Po.ht]
Power Heat
Displays the current heat con-
trol power.
0.0 to 100.0% power (000
to 10000) (Two decimal
places implied for Mod-
bus.)
NA 256 R
[A-M] is set to
[auto] and at least
one output is set to
[hEAt].
[Po;CL]
[Po.CL]
Power Cool
Displays the current cool con-
trol power.
0.0 to 100.0% power (000
to 10000) (Two decimal
places implied for Mod-
bus.)
NA 257 R
[A-M] is set to
[auto] and at least
one output is set to
[Cool].
[A-M]
[A-M]
Auto-Manual Mode
Set the control mode.
[auto] (0)
[Man] (1)
[auto]
(0)
25 R/W Always appears.
[`Aut]
[ Aut]
Autotune
Start an autotune.
[`OFF] off (0)
[``On] on (1)
[`OFF]
(0)
215 R/W At least one output
is set to [hEAt] or
[Cool].
[t;tun]
[t.tun]
TRU-TUNE+™ Enable
Enable or disable the TRU
TUNE+
adaptive tuning
feature.
[``no] No (0)
[`yES] Yes (1)
[`yES]
350
rw
TRU-TUNE+
version
only. (SD_ E - _ _ _ _
- _ _ _ _ ).
[`CAL]
[ CAL]
Calibration Offset
Offset the input reading.
-999 to 999
(-999000 to 999000)
0.0 *85, 86 R/W Always appears.
[ht;m]
[ht.M]
Heat Control
Method Set the heat control
method.
[`OFF] off (0)
[`PID] PID (1)
[on;of] on-off (2)
[`PID]
(1)
213 R/W At least one output is
set to [hEAt].
[Pb;ht]
[Pb.ht]
Proportional Band Heat
Set the proportional band for
the heat outputs.
1 to 999°F, if [`Sen] is
set to [``tc] or [`rtd]
(1000 to 999000)
0.000 to 999 units, if
[`Sen] is set to [`mA]
or [uolt]. (0000 to
999000)
25 25 *335, 336 R/W
*339, 340 R/W
At least one output
is set to [hEAt]
and [ht;m] is set to
[`PId].
[It;hc]
[It.hc]
Integral
Set the PID integral in
seconds per repeat for all
outputs.
0.00 to 3,600 seconds per
repeat (0000 to 3600)
0.00: disabled
180.0 *343, 344 R/W
TRU-TUNE+
ver-
sion only. (SD_E - _ _
_ _ - _ _ _ _ ). [ht;m]
and/or [CL;m] is set
to [`PId].
Note: Parameters appear in the Operations Page only if activated from the programming page. See page 22 for Operations Page defaults.
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature param-
eters through Modbus are in °F, by default.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.
**** This value multiplied by 100 equals the percent power.