Watlow Series SD 44 Chapter 8 Programming
Programming Page Example
An oven manufacturer wants users of their ovens to have
easy access to the Series SD PID parameters. They also
want to limit access to other parameters they do not
want them to change. This can be achieved by custom-
izing the Operations Page. The Programming Page con-
figuration determines which parameters appear on the
Operations Page. The static set point version (SD_C-_ _
_ _- _ _ _ _.) has 20 Programming Page locations, P1 to
P20. The profiling version (SD_R-_ _ _ _- _ _ _ _.) has 23
Programming Page locations, P1 to P23.
The oven manufacturer wants only these parameters to
appear on the Operations Page:
• Heat Output Power
• Fahrenheit/Celsius
• Autotune
• Modbus Device Address
To go to the Programming Page, press the Advance
and Infinity
ˆ
keys for six seconds from the Home Page.
{Prog}
will appear in the upper display and
{page}
in
the lower display.
• Press the Advance Key to move through the pa-
rameter prompts.
Press the Up ¿ or Down ¯ keys to change the pa-
rameter value.
Press the Infinity Key ˆ at any time to return to
the Home Page.
On the Programming Page, select the following settings:
[Po;ht] [~C-F] [~Aut] [Addr] [none] [none]
[~~P1] [~~P2] [~~P3] [~~P4] [~~P5] thru [~P20]
To access the Operation Page parameters, press the
Infinity Key ˆ
to return to the Home Page. Press the
Advance Key
to see the Operation Page parameters.
Only the parameters selected on the Programming Page
appear on the Operations Page.
[~~50] [~~~F] [~Off] [~~~1}
[Po;ht] [~C-F] [~Aut] [Addr]