Troubleshooting Alarms and Errors
Indication Probable Cause(s) Corrective Action
Error Code Messages ([----] in the upper display indicates a Series V4 error; error code number is visible in
bottom display)
Sensor input generated a value lower than allowable
signal range, or A/D circuitry malfunctioned. Enter a
valid input. Make sure
[``In]
parameter (Setup
Menu) matches your sensor and DIP switches are set
accordingly.
Microprocessor is faulty; consult factory.
• Unless power interruption occurred while controller
was storing data, nonvolatile memory is bad; consult
factory.
A/D circuit is underrange. Check sensor; if function-
ing properly, consult factory. Make sure
[``In]
parameter (Setup Menu) matches your sensor and
DIP switches are set accordingly.
A/D circuit is overrange. Check sensor; if functioning
properly, consult factory. Make sure
[``In]
parame-
ter (Setup Menu) matches your sensor and DIP
switches are set accordingly.
• Sensor underrange error (applies
only to RTD units)
• Configuration error.
• Non-volatile checksum error.
A/D underflow error.
A/D overflow error.
[----] [`Er2]
[----] [`Er4]
[----] [`Er5]
[----] [`Er6]
[----] [`Er7]
• Check the alarm logic for compatibility with system
peripherals and annunciators.
• Check the power limit setting
• Check the operation mode.
• Check the alarm output function.
• Check the °C or °F setting.
• Check the calibration offset value; set it to a lower
level.
Alarm may be latched.
Alarm set points may be incorrect..
Alarm hysteresis may be incorrect.
• Input may be in error condition.
Alarm won’t
occur.
• Configure output as an alarm.
Check alarm set points.
To clear the alarm, correct the alarm condition; check
to see if the alarm is latched.
• Check the alarm sides setting.
• Check the alarm type setting.
Alarm output may be off.
Alarm set points may be incorrect.
Alarm may be silenced.
Alarm sides may be incorrect.
Controller may be in diagnostics
mode.
Alarm won’t
occur.
Alarms
Check switches, fuses, breakers, interlocks, limits,
connectors, etc. for energized condition and proper
connection.
Measure power upstream for required level. Check part
number for input power required.
Check wire size.
Check for bad connections.
Power to unit may be off.
Fuse may be blown.
Breaker may be tripped.
Safety interlock door switch, etc.
may be activated.
Separate system limit control
may be latched.
Wiring may be open.
Input Power may be incorrect.
• No power.
Power