Watlow Series SD31 ■ 8 ■ Chapter 2 Install and Wire
Figure 8a — 0 to 20 mA Process Input
(all model numbers)
• Input impedance 100 Ω, dc only
• Controller does not supply power for the current loop
Figure 8b — Output 1 Mechanical Relay
SD31 - _ J _ _ - _ _ _ _
• Form A contact
• 2 A, resistive
• 125 VA pilot duty, 120/240VÅ (ac), inductive
• See Quencharc note
• 240VÅ (ac) maximum
• 30VÎ (dc) maximum
• For use with ac or dc
• Minimum load current 10 mA
• Output does not supply power
Figure 8c — Output 1 Solid-state Relay
SD31 - _ K _ _ - _ _ _ _
• Form A contact
• 0.5 A maximum, resistive
• 20 VA pilot duty, 120/240VÅ (ac), inductive
• See Quencharc note
• 24 to 240VÅ (ac)
• Minimum load current 10 mA
• Maximum leakage current 100 µA
• Not for use with direct current (dc)
• Output does not supply power
COM.
N.O.
COM.
N.O.
ç
WARNING: Process input may
not have sensor break protec-
tion. Outputs can remain full on.
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc.) with the mechanical relay
or solid-state relay output op-
tions requires use of an R.C.
suppressor.
Watlow carries the R.C. sup-
pressor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.
Spring clamp wiring connector
note:
To insert the wire, push the wire
into the desired connection num-
ber, and it should automatically
lock into place. To remove the
wire, press and hold the orange
release tab with a small screw-
driver. Pull the wire out of the
connection. Solid or tinned wire
recommended.