Watlow Series SD31 28 Chapter 5 Setup
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.
Caution: Writing to registers continuously, such as ramping set points via comms, will damage the SD31 EEPROM memory. See page 59.
[``rP]
[ rP]
Ramping Mode
Select when the control set point ramps to
the defined end set point.
[`OFF]
off (0)
[`Str]
ramps on start-up
only (1)
[``On]
ramps at start-up or
any set point change (2)
[`OFF]
(0)
266 R/W
Always active.
[rP;Sc]
[rP.Sc]
Ramp Scale
Select the scale of the ramp rate.
[hour]
degrees/hour (0)
[Min]
degrees/minute (1)
[hour]
(0)
267 R/W
[``rP]
is set to
[`Str]
or
[``On]
.
[rP;rt]
[rP.rt]
Ramp Rate
Set the rate for the set point ramp.
0 to 9999
(0000 to 9999000)
100
*268, 269
R/W
[``rP]
is set to
[`Str]
or
[``On]
.
Does not appear if
[``rP]
is set to
[`OFF]
.
[Addr]
[Addr]
Modbus Device Address
Set the device address for communica-
tions. Every controller on a network must
have a unique address.
1 to 247 1
This can
only be set
from the
controller
front panel.
Output 2 is a communi-
cations output.
(SD_ _ - _ _ U _ - _ _ _ _ )
[bAud]
[bAud]
Baud Rate
Set the baud rate at which the communi-
cations occurs.
[9600]
9600 baud
[`19;2]
19,200 baud
[`38;4]
38,400 baud
[9600]
This can
only be set
from the
controller
front panel.
Output 2 is a communi-
cations output.
(SD_ _ - _ _ U _ - _ _ _ _ )
[`LOC]
[ LOC]
Lockout
Set the security level for the user inter-
face.
[```0]
(0) No lockout
[```1]
(1) Set Point,
Auto/Manual, alarms only
[```2]
(2) Set Point,
Auto/Manual, only
[```3]
(3) Set Point only
[```4]
(4) Full lockout
See the Features Chapter
for details.
[```0]
(0)
43 R/W
Always active.