Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Spring clamp wiring connector
note:
To insert the wire, push the wire
into the desired connection num-
ber, and it should automatically
lock into place. To remove the
wire, press and hold the orange
release tab with a small screw-
driver. Pull the wire out of the
connection. Solid or tinned wire
recommended.
Note: To prevent ground loops,
isolation needs to be maintained
from input to output when using
switched DC or analog process
outputs.
ç
WARNING: Process input may
not have sensor break protec-
tion. Outputs can remain full on.
Watlow Series SD31 ■ 7 ■ Chapter 2 Install and Wire
Figure 7a — Thermocouple Input
(all model numbers)
Thermocouples are polarity sensitive. The negative lead (usually red) must be
connected to terminal 11.
• Input impedance: >20 MΩ
Figure 7b — RTD Input (100
ΩΩ
DIN curve 0.00385
ΩΩ
/
ΩΩ
/°C)
(all model numbers)
Terminals 8 and 11 must be shorted for a two-wire RTD. For three-wire RTDs,
the S1 lead (usually white) must be connected to terminal 10.
• Nominal excitation current: 390 µA
Figure 7c — 0 to 10V
ÎÎ
(dc) Process Input
(all model numbers)
• Input impedance 20 kΩ, dc only
Figure 7d — 0 to 50mV
ÎÎ
(dc) Process Input
(all model numbers)
• Input impedance >20 MΩ, dc only