Watlow Series SD6 PID with DeviceNet 16
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
133 Get/Set Analog Output 1 Low
Scale volts
UDINT Set the low scale for analog
outputs
0.00 to 10.00 V if output
is set to Volts (default =
0.00) (* 1000)
134 Get/Set Analog Output 1 High
Scale mA
UDINT Set the high scale for analog
outputs
0.00 to 20.00 mA if output
is set to mA (default =
20.00 mA) (* 1000)
135 Get/Set Analog Output 1 High
Scale volts
UDINT Set the high scale for analog
outputs
0.0 to 10.00 V if output is
set to Volts (default =
10.00 V) (* 1000)
136 Get/Set Output 2 Function USINT Set the output 2 function (0) OFF
(1) Process Alarm
(2) Deviation Alarm
(3) Heat Control (default)
(4) Cool Control
137 Get/Set Control Method 2 USINT Set the output 2 control type
Only used with PID control
(0) Fixed Timed Base
(default)
(1) Variable Time Base
138 Get/Set Fixed Time Base 2 UDINT Set the time base for fixed
time based control
1.0 to 60.0 if Output 2 is a
mechanical relay
0.1 to 60.0 if Output 2 is
not a mechanical relay
(* 1000)
Defaults:
20.0 mechanical relay
5.0 solid-state relay
1.0 switched DC
139 Get/Set Power Limit 2 UINT Set the maximum power out-
put for a control output.
1.0 to 100.0%
(default = 100.0%)
140 Get/Set Output Power Scale Low
2
UINT Set the low end of the range
within which the output will
scale.
0 to 100%
(default = 0)
141 Get/Set Output Power Scale High
2
UINT Set the high end of the range
within which the output will
scale.
0 to 100%
(default = 100)
142 Get/Set Output Non-linear
Function 2
USINT Select a non-linear output
curve to match the response
of your system.
(0) OFF (default)
(1) Curve 1
(2) Curve 2
143 Get/Set Alarm 1 Hysteresis UDINT Set the hysteresis for an
alarm. This determines how
far into the safe region the
input needs to move before
the alarm can be cleared.
1.0 to 999.0 (* 1000)
(default = 1.0)
144 Get/Set Alarm 1 Logic BOOLEAN Select the alarm output condi-
tion in the alarm state.
(0) Closed on alarm
(default)
(1) Open on alarm