Watlow Series SD6 PID with DeviceNet ■ 32 ■
Class Services:
• 0x0E GET ATTRIBUTE SINGLE
Instance Services:
• 0x0E GET ATTRIBUTE SINGLE
• 0x10 SET ATTRIBUTE SINGLE
NOTE: All successful Explicit Message Responses from a SET service will contain no data. The
response will be a two-byte message containing the requester’s MAC ID and Service Code (with R/R
bit set).
Attribute # Access Rule Name DeviceNet
Data Type
Description of Attribute Semantics of Values
107 Get/Set Event Output 2 BOOLEAN Selects whether output 2 is
on or off during step
(0) - OFF (default)
(1) - ON
108 Get/Set Wait-for Process
Enable
BOOLEAN Select to enable Wait-for
Process value
(0) - NO (default)
(1) - YES
109 Get/Set Wait-for Process
value
DINT Selects wait-for value before
step timer starts
-1999 to 9999(*1000)
Default = 75
110 Get/Set Jump File UINT Selects the file which is to be
jumped to
1 to 4. Default = 1
111 Get/Set Jump Step UINT Selects the step which is to
be jumped to
1 to 10. Default = 1
112 Get/Set Jump Count UINT Indicates the number of time
the jump is to be done.
0 to 9999. Default = 1
113 Get/Set Link File UINT Selects the file to link to. 1 to 4. Default = 1
114 Get/Set End BOOLEAN Selects the state of the con-
trol and auxilary outputs
when a profile is ended
(0) - Off (default)
(1) - Hold
Komentarze do niniejszej Instrukcji