Watlow Series SD6 PID with DeviceNet 19
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
170 Get/Set Process Scale High mV UDINT Set the high scale for
process input
0.00 to 50.00 mV
(*1000) (when Sensor
Type set to mV, default =
50.00 mV)
171 Get/Set Process Input Low error
mA
INT Sets the low process value
that will cause an error to
occur for the process input
-1.00 to 10.00 mA (*100)
(Default = -1.00 mA)
172 Get/Set Process Input Low error
Volts
INT Sets the low process value
that will cause an error to
occur for the process input
-1.00 to 5.00 V
(*100)(Default = -1.00 V)
173 Get/Set Process Input Low error
mV
INT Sets the low process value
that will cause an error to
occur for the process input
-1.00 to 25.00 mV (*100)
(Default = -1.00 mV)
174 Get/Set Process Input High error
mA
UINT Sets the high process value
that will cause an error to
occur for the process input
10.00 to 21.00 mA
(*100) (Default = 21.00
mA)
175 Get/Set Process Input High error
Volts
UINT Sets the high process value
that will cause an error to
occur for the process input
5.00 to 11.00 V (*100)
(Default = 11.00V)
176 Get/Set Process Input High error
mV
UINT Sets the high process value
that will cause an error to
occur for the process input
25.00 to 51.00 mV
(*100) (Default =
51.00mV)
177 Get/Set Output 1 Retransmit
Source
BOOLEAN Set the control variable that
the retransmit signal repre-
sents
(0) - Process (default)
(1) - Set Point
178 Get/Set Output 1 Retransmit Low
Scale
DINT Set the low scale for the
retransmit output
-1999.0 to 9999.0
(*1000) (Default = 0)
179 Get/Set Output 1 Retransmit
High Scale
DINT Set the high scale for the
retransmit output
-1999.0 to 9999.0
(*1000) (Default = 500)
180 Get/Set Output 1 Retransmit
Offset
DINT Set the high scale for the
process output
-999.0 to 999.0 (*1000)
(Default = 0)
181 Get/Set RTD Linearization USINT RTD type (0) DIN (default)
(1) Unused 1
(2) Unused 2