Watlow Series SD6 PID with DeviceNet 24
Table 29. Factory/Calibration Class Attributes
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
1 Get Revision UINT Revision of this object The revision level of this
object (currently 1)
2 Get Max Instance UINT Max allowed Instances of this
object
Always 1 for this Class
Class Services:
0x0E GET ATTRIBUTE SINGLE
Instance Services:
0x0E GET ATTRIBUTE SINGLE
0x10 SET ATTRIBUTE SINGLE
NOTE: All successful Explicit Message Responses
from a SET service will contain no data. The
response will be a two-byte message containing
the requester’s MAC ID and Service Code (with
R/R bit set).
Factory/Calibration Object
Class Code: 67hex
Factory/Calibration Object
The Factory/Calibration Object provides access to parame-
ters that contain diagnostics information, calibration and
restore-parameter functions.
Table 28. Factory/Calibration Revision History
Revision Description
01 Initial Release
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
130 Get/Set Alarm 2 Low Temperature DINT Set the low alarm set point. -1999 to 0 (* 1000) if
Sensor Type is set to
Thermocouple or RTD
(default = -999)
-1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.
(default = 32)
131 Get/Set Alarm 2 Low Process DINT Set the low alarm set point. -1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.
(default = 32)
132 Get/Set Event Output 1 BOOLEAN Set event output 1 to an on or
off state.
(0) OFF (default)
(1) ON
133 Get/Set Event Output 2 BOOLEAN Set event output 2 to an on or
off state.
(0) OFF (default)
(1) ON