Watlow Series SD6 PID with DeviceNet ■ 25 ■
Table 30. Factory/Calibration Object Instance Attributes
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
100 Get Ambient Temperature DINT Displays the current calculat-
ed ambient temperature.
-50.0 to 300.0°F
(* 1000)
101 Get Output 1 Process Value UINT Monitors Process Output 1
value via DeviceNet
00.00 to 22.00 units
102 Get/Set Restore Factory
Calibration
BOOLEAN Replaces the user calibration
parameters with the factory
calibration parameters.
(0) NO (default)
(1) YES
103 Get/Set Restore User Settings BOOLEAN Restores the customer-config-
ured settings.
(0) NO (default)
(1) YES
104 Get/Set Save User Settings BOOLEAN Saves the current customer-
configured settings.
(0) NO (default)
(1) YES
105 Get/Set Default Parameters BOOLEAN Reset all parameters to their
default values.
(0) NO (default)
(1) YES
106 Get Output 1 Type USINT Displays the hardware type for
Output 1.
(0) None
(1) DC/Open Col.
(2) Mech. Relay
(3) S.S. Relay
(4) Process
107 Get Output 2 Type USINT Displays the hardware type for
Output 2.
(0) None
(1) DC/Open Col.
(2) Mech. Relay
(3) S.S. Relay
(4) Process
108 Get Software ID UINT Software ID number 0 to 9999
109 Get Software Build Number UINT Software built number 0 to 9999 Build Number
110 Get Serial Number UDINT Serial number 0 to 99999999