Watlow Series SD6 PID with DeviceNet 29
Table 36. Profiling Object Instance Attributes
Attribute # Access Rule Name DeviceNet
Data Type
Description of Attribute Semantics of Values
100 Get/Set Profile Type BOOLEAN Set the profile ramp to time
based or rate based
(0) - Time (default)
(1) - Rate
101 Get/Set Profile Start BOOLEAN Selects where the profile
begins the starting set point
of the profile, current static
set point or current process
temperature.
(0) - Set Point (default)
(1) - Process
102 Get/Set Guaranteed Soak
Deviation Enable
BOOLEAN Enables the guaranteed
soak deviation function in
profiles
(0) - Disabled (default)
(1) - Enabled
103 Get/Set Guaranteed Soak
Deviation Value
UDINT Set the value of deviation
allowed by the guaranteed
soak deviation function
1 to 999 (*1000)
(default = 1)
104 Get Profile State USINT Indicates current profile sta-
tus
(0) - Off (default)
(1) - Holding
(2) - Running
(3) - Pre-run check
failed when starting the
profile
(4) - Pre-run failed
when resuming the pro-
file
105 Get Jump Count Step
Enabled
BOOLEAN Indicates whether a Jump
Step is currently being exe-
cuted
(0) - Profile is not run-
ning or is running and
currently not executing
a Jump step (default)
(1) - Profile is executing
a Jump step
106 Get/Set Start File Number UINT Selects the file to start run-
ning
1 to 4
(default = 1)
107 Get/Set Start Step Number UINT Selects the profile step to be
run
1 to 10
(default = 1)
108 Get/Set Profile Select USINT Selects what to do when a
profile is on hold
(0) - Off
(1) - Resume
(2) - Hold
109 Get Guaranteed Soak
Deviation Message
BOOLEAN Monitors guaranteed soak
deviation status
(0)- Disabled (default)
(1)- Enabled
110 Get File Running UINT File number that is currently
running
1 to 4
111 Get Step Running UINT Step number that is currently
running
1 to 10
112 Get End Set Point Value DINT Set point value reached at
the end of current step
(Splo) to (sphi)