Watlow Series SD6 PID with DeviceNet 18
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
157 Get/Set Active Displays USINT
Select which display are
active.
(0) Both displays (default)
(1) Lower display only
(2) Upper display only
158 Get/Set Ramping Mode USINT
Select when the control set
point ramps to the defined end
set point.
(0) OFF (default)
(1) Ramps on start-up
(2) Ramps on any set
point change
159 Get/Set Ramp Scale BOOLEAN
Select the scale of the ramp
rate.
(0) Degrees / hour
(default)
(1) Degrees / minute
160 Get/Set Ramp Rate UDINT
Set the rate for the set point
ramp.
0 to 9999 (* 1000)
(default = 100)
161 Get/Set Lockout USINT
Set the security level for the
user interface.
(0) No Lockout (default)
(1) Set Point,
Auto/Manual, Alarms, only
(2) Set Point,
Auto/Manual, only
(3) Set Point only
(4) Full Lockout
162 Get/Set Alarm Acknowledge 1 BOOLEAN
Alarm acknowledge for output 1. (0) No
(1) Yes
163 Get/Set Alarm Acknowledge 2 BOOLEAN
Alarm acknowledge for output 2. (0) No
(1) Yes
164 Get/Set AC Line Frequency BOOLEAN Sets the frequency of the
applied AC line source
(0) - 60 (default)
(1) - 50
165 Get/Set Profile Type BOOLEAN Sets the profile ramp to time
based or rate based
(0) - time based (default)
(1) - ramp based
166 Get/Set Profile Start BOOLEAN Selects where the profile
begins the starting set point,
current static set point or
process temperature.
(0) - set point (default)
(1) - process
167 Get/Set Guaranteed Soak
Deviation Enable
BOOLEAN Enables the guaranteed
soak deviation function in
profiles
(0) - disabled (default)
(1) - enabled
168 Get/Set Guaranteed Soak
Deviation Value
UDINT Sets the value of deviation
allowed
1 to 999 (*1000)
(default = 1)
169 Get/Set Process Scale Low mV UDINT Set the low scale for process
input
0.00 to 50.00 mV
(*1000) (when Sensor
Type set to mV, default
= 0.00 mV)