Watlow EZ-ZONE
®
RML Module • 104 • Chapter 6 Features
Output
Off
Output
Digital
Output Low Power Scale
Output Time Base
Output Control
Output High Power Scale
Output Low Power Scale
Output Time Base
Output Control
Output High Power Scale
Output Function
Output Function Instance
Output Source Zone
Output Source Error
Output Function
Output Function Instance
Output Source Zone
Output Source Error
Output Value
Output Value
Error
Error
Security Function
Note:
Set on a Zone by Zone basis affecting any access
using Standard Bus communications. Does not af-
fect field protocols.. This is independent of the RUI
Security Setting.
If the Password is enabled, the user must enter the Pass-
word to get to menus that have been blocked due to lock
level settings. Rolling passwords require a new password
each time the power has been cycled to the controller. It
will be different for every controller. The administrator
password is required to change the security settings even
if the user enters their password to override the security
settings.
Security Function Block - Overview
Instances - 1 per RML
[LoC;o] Operations Page : 1 to 3
[r;LoC] Read Lock : 1 to 5
[S;LoC] Write Security: 1 to 5
[LoC;P] Profiling Page : 1 to 3
[PAS;E] Password Enable : Off, On
[LoC;L] Locked Access Level : 1 to 5
[roL;L] Rolling Password : Off, On
[PAS;u] User Password : 10 to 999
[PAS;A] Administrator Password : 10 to 999
[CodE] Public Key : xxx
[PASS] Password : xxx
Write Security
Locked Access Level
Rolling Password
User Password
Administrator Password
Public Key
Password
Profiling Page
Read Lock
Operations Page
[LoC] Lock Menu
[FAct] Factory Page
[ULoC] Unlock Menu
[FAct] Factory Page
Komentarze do niniejszej Instrukcji