Watlow EZ-ZONE RM Limit Module Rev C Instrukcja Użytkownika Strona 23

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 127
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 22
Warning: ç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12 AWG)
single-wire termination or two 1.31
mm
2
(16 AWG)
• 0.8 Nm (7.0 in-lb.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the controller,
do not connect wires to unused ter-
minals.
Note:
Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs
to prevent ground loops.
Watlow EZ-ZONE
®
RML Module 20 Chapter 2 Install and Wire
Limit Module Wiring (RMLx-xxxx-xxxx)
Inputs 1 through 12 Thermocouple
-
+
-
+
-
+
-
+
Ther
mocouple
S_
R_
S_
R_
S_
R_
S_
R_
Slot A, B, D
2K Ω maximum source resistance
>20 MΩ input impedance
3 microampere open-sensor detection
Thermocouples are polarity sensitive. The negative lead (usually red)
must be connected to S terminal
To reduce errors, the extension wire for thermocouples must be of the
same alloy as the thermocouple.
Input 1 - 4 (top to bottom): RMLx-(5)xxx-xxxx
Input 5 - 8 (top to bottom): RMLx-x(5)xx-xxxx
Input 9 - 12 (top to bottom): RMLx-xx(5)x-xxxx
CC
CA
CB
CZ
CX
CY
S
l
o
t
C
T+ / R+
Modbus
Common
T- / R-
Inter-module Bus
Common
+
-
CC, CA, CB - Modbus and Standard Bus EIA485 Communi-
cations (selectable via push button under zone address)
CZ, CX, CY - Inter-module Bus EIA485 Communications
Do not route network wires with power wires. Connect net-
work wires in daisy-chain fashion when connecting multiple
devices in a network
RML Part # Digit 10 is 1
Communications
CF
CD
CE
CZ
CX
CY
S
l
o
t
C
Standard Bus
Common
T- / R-
Inter-module Bus
Common
-
+
T+ / R+
CF, CD, CE - Standard Bus EIA485 Communications
CZ, CX, CY - Inter-module Bus EIA485 Communications
Do not route network wires with power wires. Connect
network wires in daisy-chain fashion when connecting
multiple devices in a network
Communications
RML Part # Digit 10 is A
Low Power
20.4 to 30.8 V Å (ac) / Î (dc)
47 to 63 Hz
Module maximum power consumption, 14 VA (ac), 7 VA
(dc)
31 Watts maximum power available for P/S part #:0847-
0299-0000
60 Watts maximum power available for P/S part #:0847-
0300-0000
91 Watts maximum power available for P/S part #:0847-
0301-0000
Class 2 or SELV power source required to meet UL compli-
ance standards
RML- ALL Model Numbers
98
99
S
l
o
t
C
power
RML Part # Digits 5, 6, 7