Watlow EZ-ZONE
®
RML Module • 54 • Chapter 4 Setup Page
RM Limit Module • Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;A]
[SFn.A]
Compare (1 to 16)
Source Function A
Set the type of function
that will be used for this
source.
[nonE] None (61)
[``Ai] Analog Input (142)
[CUrr] Current (22)
[`C;Pr] Cool Power, Control
Loop (161)
[`h;Pr] Heat Power, Control
Loop (160)
[PWr] Power, Control Loop
(73)
[`Lnr] Linearization (238)
[MAt] Math (240)
[``Pu] Process Value (241)
[`SP;C] Set Point Closed,
Control Loop (242)
[`SP;o] Set Point Open, Con-
trol Loop (243)
[`uAr] Variable (245)
None 5910
[offset 40]
0x80 (128)
1 to 16
1
- - - - 28001 uint
RWES
[`Si;A]
[ Si.A]
Compare (1 to 16)
Source Instance A
Set the instance of the
function selected above.
1 to 250 1 5914
[offset 40]
0x80 (128)
1 to 16
3
- - - - 28003 uint
RWES
[`S2;A]
[ SZ.A]
Compare (1 to 16)
Source Zone A
Set the zone of the function
selected above.
0 to 16 0 5918
[offset 40]
0x80 (128)
1 to 16
5
- - - - 28005 uint
RWES
[SFn;B]
[SFn.b]
Compare (1 to 16)
Source Function B
Set the type of function
that will be used for this
source.
[nonE] None (61)
[``Ai] Analog Input (142)
[CUrr] Current (22)
[`C;Pr] Cool Power, Control
Loop (161)
[`h;Pr] Heat Power, Control
Loop (160)
[PWr] Power, Control Loop
(73)
[`Lnr] Linearization (238)
[MAt] Math (240)
[``Pu] Process Value (241)
[`SP;C] Set Point Closed,
Control Loop (242)
[`SP;o] Set Point Open, Con-
trol Loop (243)
[`uAr] Variable (245)
None 5912
[offset 40]
0x80 (128)
1 to 16
2
- - - - 28002 uint
RWES
[`Si;B]
[ Si.b]
Compare (1 to 16)
Source Instance B
Set the instance of the
function selected above.
1 to 250 1 5916
[offset 40]
0x80 (128)
1 to 16
4
- - - - 28004 uint
RWES
[`S2;B]
[ SZ.b]
Compare (1 to 16)
Source Zone B
Set thezone of the function
selected above.
0 to 16 0 5920
[offset 40]
0x80 (128)
1 to 16
6
- - - - 28006 uint
RWES
[`Er;h]
[ Er.h]
Compare (1 to 16)
Error Handling
[``t;g] True Good (1476)
[``t;b] True Bad (1477)
[``F;g] False Good (1478)
[``F;b] False Bad (1479)
False Bad 5932
[offset 40]
0x80 (128)
1 to 16
0xC (12)
- - - - 28012 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set