Watlow EZ-ZONE
®
RML Module 58 Chapter 4 Setup Page
RM Limit Module Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;B]
[SFn.b]
Counter (1 to 16)
Source Function B
Set the type of function
that will be used for the
counter load signal.
[nonE] None (61)
[ALM] Alarm Reset (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[Ent;C] Profile Event Out C
(235)
[Ent;d] Profile Event Out D
(236)
[Ent;E] Profile Event Out E
(247)
[Ent;F] Profile Event Out F
(248)
[Ent;g] Profile Event Out G
(249)
[Ent;h] Profile Event Out H
(250)
[`FUn] Function Key (1001)
[`lgC] Logic (239)
[tMr] Timer (244)
[`uAr] Variable (245)
None 6552
[offset 40]
0x82 (130)
1 to 16
2
- - - - 30002 uint
RWES
[`Si;B]
[ Si.b]
Counter (1 to 16)
Source Instance B
Set the instance of the
function selected above.
1 to 250 1 6556
[offset 40]
0x82 (130)
1 to 16
4
- - - - 30004 uint
RWES
[`S2;B]
[ SZ.b]
Counter (1 to 16)
Source Zone B
Set the zone of the function
selected above.
0 to 16 0 6560
[offset 40]
0x82 (130)
1 to 16
6
- - - - 30006 uint
RWES
[sas;b]
[SAS.b]
Counter (1 to 16)
Source Active State B
Set what output state will
indicate on.
[high] High (37)
[LoW] Low (53)
High 6572
[offset 40]
0x82 (130)
1 to 16
0xC (12)
- - - - 30012 uint
RWES
[LoAd]
[LoAd]
Counter (1 to 16)
Load Value
Set the counter's initial
value.
0 to 9,999 0 6574
[offset 40]
0x82 (130)
1 to 16
(13)
215 30013 uint
RWES
[trgt]
[trgt]
Counter (1 to 16)
Target Value
Set the value that will turn
the output value on.
0 to 9,999 9,999 6576
[offset 40]
0x82 (130)
1 to 16
0xE (14)
216 30014 uint
RWES
[`lAt]
[ LAt]
Counter (1 to 16)
Latching
If enabled, output will latch
when count equals target
value.
No (59)
Yes (106)
No 6582
[offset 40]
0x82 (130)
1 to 16
0x11 (17)
218 30017 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set