Watlow EZ-ZONE
®
RML Module 74 Chapter 5 Factory Page
RM Limit Module Factory Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[CUSt]
[FCty]
Custom Setup Menu
[`par]
[ Par]
Custom Menu
Parameter 1 to 30
Select the parameters that
will appear in the Home Page
when using the RUI.
The Parameter 1 value will
appear in the upper display
of the Home Page. It can-
not be changed with the Up
and Down Keys in the Home
Page.
The Parameter 2 value will
appear in the lower display
in the Home Page. It can be
changed with the Up and
Down Keys, if the parameter
is a writable one.
Scroll through the other Home
Page parameters with the
Advance Key
.
[nonE] None (61)
[`Pro] Process (75)
[`i;CA] Input Calibration
Offset (1196)
[`C_F] Display Units
(156)
[USr;r] User Restore Set
(227)
[`A;Lo] Alarm Low Set
Point (42)
[`A;hi] Alarm High Set
Point (78)
[`A;hy] Alarm Hysteresis
(97)
[`LL;S] Limit Low Set
Point (181)
[`Lh;S] Limit High Set
Point (182)
[`L;hy] Limit Hysteresis
(183)
[`l;st] Limit Status
(1668)
CUSt] Custom Menu
(180)
Process
Limit
Status
- - - - - - - - - - - - 14005
uint
RWES
[`iid]
[ iid]
Custom Setup (1 to 30)
Instance ID
Select the parameters that will
appear in the Home Page.
1 to 24 - - - - - - - - - - - - - - - - 14003 uint
RWES
[`LoC]
[FCty]
Security Setting Menu
[LoC;o]
[LoC.o]
Security Setting
Operations Page
Change the security level of
the Operations Page.
1 to 3 2
- - - - - - - - - - - - - - - -
- - - -
[pas;e]
[LoC.P]
Security Setting
Password Enable
Turn security features on or
off.
[`off] Off
[``on] On
Off
- - - - - - - - - - - - - - - -
- - - -
[rLoC]
[rLoC]
Security Setting
Read Lock
Set the read security clear-
ance level. The user can ac-
cess the selected level and all
lower levels.
If the Set Lockout Security
level is higher than the Read
Lockout Security, the Read
Loc
kout Security level takes
priority.
1 to 5 5
- - - - - - - - - - - - - - - -
- - - -
Note: Some values will be rounded off to fit in the four-character display. Full values can
be read with another interface.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-